© Burns Engineering Thermowell Selection and Application
Thermowell Selection and Application
If you are experiencing audio problems please call the teleconference number below
1-408-600-3600Access code 660 637 935
Bill Bergquist, Sr. Applications EngineerJeff Wigen, National Account Manager Jeff Bill
2
© Burns Engineering Thermowell Selection and Application
The thermowell used with your temperature sensor provides critical protection, access, and measurement integrity. We’ll shed some light on how, why, and when to apply this important device.
Thermowell basics• Purpose• Types• Process connection styles• Materials, coatings and surface finish
Performance• Wake frequency & strength• Immersion length• Time response
Custom designsSpecifying
• Definitions/codes• Typical drawing• Details• Testing & certifications• Options
Preventive Maintenance Selection Checklist
What We’ll Cover
3
© Burns Engineering Thermowell Selection and Application
Why use a thermowell?Protect the temperature sensor from:
• Excessive pressures• Excessive material velocities & viscosities• Corrosion• Erosion
Simplify maintenance• Sensor replacement without draining the system• Eliminate potential for contamination – system stays closed• Protection increases potential life of the sensor
Improve temperature measurements
Thermowell Basics - Purpose
A thermowell’s main purpose is to protect the temperature sensor to insure long life and accurate measurement. Maintenance is aided by allowing the sensor to be removed without having to drain the pipe or tank. Sensor changes can be done on the fly.
4
© Burns Engineering Thermowell Selection and Application
Thermowell typesSteppedTaperedStraightSanitaryProtection tube
• Typically made from pipe• Usually not suited for RTDs
Thermowell Basics - Types
Thermowell types are designated by the style of stem or wetted portion of the well. Protection tubes are typically used for thermocouples and are not suited for use with RTDs because they do not provide enough support for the sensor. Most thermowells are machined from bar stock to insure integrity for high pressure applications. Flanges are joined to a thermowell stem most commonly by a welding process. Smaller wells may be constructed from tubing and have the end welded closed and a process connection welded on. These are typically used in low pressure applications.
5
© Burns Engineering Thermowell Selection and Application
Thermowell Basics - Stem Types
Stepped
Tapered
Straight
Stepped, sometimes referred to as reduced tip, wells are usually ¾” diameter and step down to ½” diameter to improve time response. Tapered wells are a balance between strength and time response. Straight wells are specified where increased life is desired due to corrosion or erosion.
6
© Burns Engineering Thermowell Selection and Application
Connection stylesFlange
• ANSI B16.5• Van Stone
Socket weldWeld-inThreadedSanitary flangeO-Ring
Thermowell Basics - Process Connections
Connections to the process are accomplished with tapered pipe threads or adaptations of pipe or sanitary tubing flange connections. A blank or blind flange is modified to accept the thermowell stem and then easily attaches to standard flanges. Weld‐in styles are used for convenience or where exposed threads may collect contaminants such as in food processing or pharmaceutical production. A specialty type of connection incorporates an O‐ring to seal inside a sleeve welded to a tank. Sometimes referred to as an Ingold® fitting after the company that invented it for ph and oxygen sensors.
7
© Burns Engineering Thermowell Selection and Application
Thermowell Basics - Process Connections
These are just a few of the several styles available. Any imaginable pipe or tubing connection style either has been or could be adapted to a thermowell process connection.
8
© Burns Engineering Thermowell Selection and Application
Sanitary Weld-In
A sanitary weld‐in style such as this one is used in sanitary process tanks where cracks and crevices are not desired.
9
© Burns Engineering Thermowell Selection and Application
Sanitary Flange
This is a thermowell with a sanitary flange connection which is sometimes referred to as a Tri‐Clamp® connector. It is the most common style of sanitary connection. The high polish and large radius between stem and flange improve corrosion resistance and make cleaning easier.
10
© Burns Engineering Thermowell Selection and Application
Sanitary with Process & Instrument Flange
Another style of sanitary well uses a sanitary flange for attachment of the temperature sensor.
11
© Burns Engineering Thermowell Selection and Application
Sanitary Process and Instrument Flange
12
© Burns Engineering Thermowell Selection and Application
Sanitary – Easy Access Tri-Clamp
No tools are required to install or remove the sensor which makes for easier maintenance.
13
© Burns Engineering Thermowell Selection and Application
O-Ring
The most common style of instrument connection is a ½” NPT female thread as shown here on this O‐ring style well. This style well installs into a sleeve welded to a tank which accepts the well and the threaded nut holds it in place. A tight fit insures that the O‐ring seals securely.
14
© Burns Engineering Thermowell Selection and Application
Process connection selectionThread size
• Typically tapered pipe thread
Flange size and rating• Gasket surface type
– Raised– Flat– RTJ
Lag length• Added thermowell length outside process to reach through
insulation
Brass or SS plug for test wells
Thermowell Basics - Process Connections
When selecting a process connection there are several things to consider. Threaded connections are the easiest, flange connection require a flange size, pressure rating, and gasket surface style. Lag length is an extension of the non‐wetted portion of the well to reach through insulation or other obstacles to provide wrench access. Typically specified for threaded wells. Test wells that sit empty for long periods of time should have a plug in the instrument connection to prevent debris from entering.
15
© Burns Engineering Thermowell Selection and Application
Factors to considerDefine the conditions
• Corrosion/erosion• Temperature• Pressure• Fluid Properties
Match the pipe or tank materialsRefer to corrosion charts
Materials
Material selection can be as simple as choosing the same material as the tank or pipe where it is to be installed. This works most of the time but there are exceptions. In the case of corrosion or erosion an object placed into a flow is more susceptible to those effects and a different material will be necessary to provide longer life. There are corrosion charts available from thermowell manufacturers that list the preferred material for chemicals at different conditions.
16
© Burns Engineering Thermowell Selection and Application
Materials – Corrosion
Condition MaterialChemical
Material selection tables are available for numerous chemicals and conditions. Note that concentration and temperature have an influence on the recommended material. The higher the temperature and/or concentration the more corrosive the chemical can be.
17
© Burns Engineering Thermowell Selection and Application
Corrosion
Photo courtesy of Alloy Engineeringhttp://www.thermowells.com/library.html
Choosing the wrong material can result in failure of the well. Here the tip has corroded away and allowed the process fluid to leak inside the well.
18
© Burns Engineering Thermowell Selection and Application
Corrosion
Photo courtesy of Alloy Engineeringhttp://www.thermowells.com/library.html
This is a view inside the tip section showing corrosion on the inside from the leaking process fluid.
19
© Burns Engineering Thermowell Selection and Application
MaterialsCobalt-Chromium (Stellite®)Cobalt-Nickel (Wallex®)Tungsten Carbide
Silicon Carbide (Hexoloy®)Alumina
Materials - Erosion
Photo courtesy of Lisa Danielson
Particles suspended in a fluid or powdered materials can cause erosion of the well over time. There are several materials available to slow down the erosion. Most are hard materials that are applied through a welding or spraying process. Sometimes just picking the correct thermowell material is sufficient to minimize the erosion affects.
20
© Burns Engineering Thermowell Selection and Application
MaterialsMetalsPlasticCeramicSurface coatings
• Teflon• Tantalum• Ceramic• Hard facing
Surface finish• Improved corrosion resistance• Sanitary applications
– Electropolish– Passivation
Materials - Selection
A variety of materials can be used to construct thermowells. Surface coatings can be used to improve corrosion and erosion resistance. Plastics such as Teflon are highly corrosion resistant and ceramics offer high temperature capabilities and can be a good choice for erosive applications. Tantalum is used for acid resistance and can be applied as a sleeve or it can be bonded to the surface of nearly any thermowell style. Improving the surface finish will increase corrosion resistance and make it easier to clean. Fewer ridges and crevices means a smaller surface area for the corrodent to attack. Electropolishing or passivating the surface further increases corrosion resistance.
21
© Burns Engineering Thermowell Selection and Application
Materials
Sometimes less expensive materials turn out to be the best choice. Originally a Teflon plated metal well was used for monitoring the temperature of an acidic waste product. Teflon plating is easily damaged (think of your frying pan) and the acid quickly ate away the metal well causing it to leak. The solution was to use standard 3” PVC pipe to construct the well which was about 10 ft long and attached with a flange connection. An internal well was made with ½” PVC to house the temperature sensor allowing it to stick out a couple inches for better time response.
22
© Burns Engineering Thermowell Selection and Application
Positive Material Identification (PMI)
Positive Material Identification (PMI) refers to the identification and analysis of various metal alloys based on their chemical composition in nondestructive testing (NDT). Measurement results are shown in the form of elemental concentration in percentage or by specific alloy name such as SS316L or Inconel 625. PMI is a field‐testing method made possible by the portability of most PMI analyzers. These instruments also can be used in the laboratory The X‐Ray Fluorescence Technique XRF XRF instruments work by exposing a sample to a beam of X‐rays. The atoms of the sample absorb energy from the X‐rays, become temporarily excited and then emit secondary X‐rays. Each chemical element emits X‐rays at a unique energy. By measuring intensity and characteristic energy of the emitted X‐rays, an XRF analyzer can provide qualitative and quantitative analysis regarding the composition of the material being tested.
23
© Burns Engineering Thermowell Selection and Application
Measurement accuracyWake frequency and strength calculations
• ASME PTC 19.3 TW-2010
Immersion length• Elbow well
Time response• Heat transfer paste• Bore and probe diameter
Performance
Measurement accuracy can be adversely affected by a thermowell unless a few precautions are taken. Wake frequency and strength calculations are probably the most important. These calculations will tell you how long the well can be immersed into your process based on the flow conditions (more on this later). This has to be balanced with the accuracy needs of the sensor to be immersed sufficiently to prevent stem conduction or immersion error. Finally, time response is slower with the addition of a thermowell and for processes that change temperature rapidly this can be a significant error source.
24
© Burns Engineering Thermowell Selection and Application
ASME PTC 19.3 TW - 2010The long awaited PTC 19.3 TW-2010 is a completely new standard that establishesthe practical design considerations for thermowell installations in power andprocess piping. This code is an expanded version of the thermowell sectioncontained in the PTC 19.3-1974, and incorporates the latest theory in the areasof natural frequency, Strouhal frequency, in-line resonance and stress evaluation.ASME responded to changing industry demands for a more comprehensive setof thermowell evaluations. Key enhancements over the 1974 edition include:
• Expanded coverage for thermowell geometry• Natural frequency correction factors for mounting compliance,
added fluid mass, and sensor mass• Consideration for partial shielding from flow• Intrinsic thermowell damping;• Steady state and dynamic stress evaluations• Improved allowable fatigue limit definition.
ASME PTC 19.3 TW-2010
Excerpted from ASME website: http://staging.files.asme.org/Catalog/Codes/PrintBook/25750.pdf
The new release of the thermowell section of the Power Test Code incorporate the latest theory for wake frequency and strength calculations . If you’re a piping designer all this probably means a lot to you. For someone selecting a thermowell it may be a little like learning how to build a chainsaw to cut down a tree. Interesting but not really necessary. Your thermowell supplier will provide the calculations based your process conditions and desired thermowell configuration. You need to know that you want the calculations done to the new 2010 version of the standard.
25
© Burns Engineering Thermowell Selection and Application
Von Kármán vortex street, by [http://www.mcef.ep.usp.br/staff/jmeneg/cesareo/Cesareo_HomePage.htmlCesareo de La Rosa Siqueira
Von Kármán Vortex
When a cylindrical object is placed in a flow there is a disturbance created on the downstream side that oscillates back and forth. The frequency of the oscillation increases as the flow rate increases. If the resonant frequency of the thermowell matches the frequency of the vortices the well will start to vibrate and will first damage the RTD and then the well will fail. There are a lot of good illustrations of this phenomena on the internet. A search for von karman or wake frequency will return several.
26
© Burns Engineering Thermowell Selection and Application
Thermowell Selection
This graph shows the acceptable flow rates for various thermowell designs and a ¼” diameter direct immersion RTD. Note that a short increase in immersion length has a large affect on the allowable flow rate.
27
© Burns Engineering Thermowell Selection and Application
Information Required
This is typical of the information that is needed to perform the calculations.
28
© Burns Engineering Thermowell Selection and Application
Stress Crack
Photo courtesy of Alloy Engineeringhttp://www.thermowells.com/library.html
An example of what can happen if the wake frequency and strength calculations are not done. This well incorporates a support part way down the stem to provide support but it wasn’t enough. A crack formed as outlined around the stem. ASME PTC 19.3 does not recommend the use of supports such as this. Shorter immersion or larger diameter are the preferred solutions.
29
© Burns Engineering Thermowell Selection and Application
Stress Crack
Photo courtesy of Alloy Engineeringhttp://www.thermowells.com/library.html
A little better view of the crack that formed.
30
© Burns Engineering Thermowell Selection and Application
Immersion Length
25°C
Direct immersion RTDs require 10 x probe diameter plus sensitive length to avoid stem conduction errors. Thermowells require about 4.5”.
200°C
A rule of thumb for minimum immersion length to avoid stem conduction error is 10 times the probe diameter plus the sensitive length of the probe. Most RTDs have a sensitive length of approximately 1.0”. So for a ¼” diameter RTD the minimum recommended immersion is 3.5”. Thermowells require about 4.5” as a minimum for best accuracy.
31
© Burns Engineering Thermowell Selection and Application
Immersion Error for 200L05ANN135TT302
-5.00
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
40.00
0 2 4 6 8 10 12
Im m ers ion Depth (Inches)
Indi
cate
d Er
ror (
% D
elta
T)
Ice Bath
100°C Oil Bath
200°C Oil Bath
Immersion Error
A thermowell/RTD assembly was immersed in a bath to determine the stem conduction at various depths. At 4.5 inches most of the error has disappeared. As you can see the error is mostly independent of the bath temperature used. The error is expressed as a percentage of the delta T between ambient and process conditions.
32
© Burns Engineering Thermowell Selection and Application
Specialty – Elbow Wells
When line size doesn’t allow for a long enough immersion length a specialty thermowell such as this can be used. Note the flare around the internal thermowell which avoids flow restriction.
33
© Burns Engineering Thermowell Selection and Application
Elbow Well Drawing
For those applications that require a thermowell, the elbow style works well if sized correctly. An immersion length of at least 4” for most applications is necessary to provide an accurate measurement. Shorter immersion lengths may work for some process fluids and flow rates.
34
© Burns Engineering Thermowell Selection and Application
Installation in a Tee
Fluid
SENSOR INSTALLEDPERPENDICULAR TO FLOW
SENSOR INSTALLEDPARALLEL TO FLOW
SENSOR INSTALLEDPARALLEL TO FLOW
Good
BetterBest
In small diameter lines there is typically not enough room to get the proper immersion length to avoid stem conduction. This illustrates three methods of modifying the piping to provide extra room. The one on the right is the best method because it provides for the flow coming directly at the tip of the sensor for less stress on the probe and it also washes out the dead lag portion of the tee.
35
© Burns Engineering Thermowell Selection and Application
Anti-Immersion?
Photo courtesy of Alloy Engineeringhttp://www.thermowells.com/library.html
Another installation method which we don’t recommend. There’s probably a joke behind this such as “it’s for room air temperature” or it makes a nice “hand hold”. Likely just the 2nd shift crew having fun with the 1st shift crew. In any case, a reminder to always double‐check your installation.
36
© Burns Engineering Thermowell Selection and Application
Performance - Time Constant
Adding heat transfer paste cuts these times nearly in half.
Time Constant is defined as the time it takes for the sensor to indicate 63.2% of a step change in temperature in water moving at 3 fps.
37
© Burns Engineering Thermowell Selection and Application
Specialty – Fast Response Tip
Time constant is about 4 seconds
A few specialty wells such as this one can improve the time constant significantly with a small diameter tip, heat transfer paste, and a special design RTD.
38
© Burns Engineering Thermowell Selection and Application
Specialty – Flow-Through Design
This well provides protection to the sensor but allows flow into the sensor for improved time response.
39
© Burns Engineering Thermowell Selection and Application
Specialty – Large Diameter Elbow
A 3” tube sanitary elbow thermowell is shown here and reveals the internal thermowell which is 3/8” diameter and has a .260” bore diameter.
40
© Burns Engineering Thermowell Selection and Application
• Process connection “P”• Immersion length “U”• Lag length “T”• Bore depth “A” – usually overall length minus ¼”• Tip diameter “D”• Root diameter “Q”• Stem style• Instrument connection• Material
Coatings• Bore diameter• Surface finish• Plug• Testing• Certifications
Specifying - Definitions/Codes
Standard variable letters are used to describe thermowell dimensions.
41
© Burns Engineering Thermowell Selection and Application
Specifying – Typical Drawing
Of these the immersion length U and the bore depth A are most commonly used for specifying the length of the sensor.
42
© Burns Engineering Thermowell Selection and Application
Thread size1/2˝, 3/4”, or 1” NPT
Socket weld 3/4˝ refers to O.D. of connection based on pipe size. 3/4” = 1.05” OD of fitting
Flange2.0˝ x 150 LB or class 1501.5˝ x 300 LB
Sanitary flange1.5˝, 2”, 2.5” etc.
• Flange size refers to the tube size it is used to connect and not the actual flange diameter. For example: 1.5” sanitary flange measures 2.0” diameter
Specifying – Some “Need to Know” Details
Some knowledge of the various types of process connections is required to choose the correct size. Threaded connections are NPT and fairly straight forward. Flange connection sizes refer to the size pipe or tube which they connect.
43
© Burns Engineering Thermowell Selection and Application
A “few” of the available certifications:• Hydrostatic internal or external pressure testing per ASTM• Dye penetrant testing per ASTM • X-ray examination per ASTM• Material certification• Wake frequency and strength calculations • Mechanical Surface Finish Certification• Canadian Registration Number (CRN)• Material Certificate of Conformance• No ADM (Animal Derived Material)• Certification that no polishing compound was used• Certification of NACE Approval• Electropolish and Surface Finish Certification• Positive material identification (PMI) • Inspection Certificate (ISO 10474, EN 10204, DIN 50049) 3.1B • Passivation• Weld Map - location & numerical identification of every weld
Specifying - Testing and Certifications
These are just a few of the possible tests that can be performed on a thermowell. Of these, the most common are material certification, wake frequency calculations, and pressure testing.
44
© Burns Engineering Thermowell Selection and Application
Some available options:• Plug and chain • Marked with tag number (customer specific information) • Open ended thermowell • 1/8” Diameter weep hole• Full weld penetration on flanged well, includes certification • British Standard Pipe process threads (BSP) • Deep Tap threads (for explosion proof applications)• Velocity collar (not recommended per the ASME standard)• Coatings for corrosion or erosion resistance• Flange facing options• Cleaned for oxygen service• Root and tip “Q” and “D” dimension options
Specifying - Options
45
© Burns Engineering Thermowell Selection and Application
Preventive maintenance• Thermowell
Bore cleaningHeat transfer compoundProduct buildup on wetted portionCracks in flange weld or leaky gasketRTD bottoms in well and spring loads
An ounce of prevention…
Thermowells typically need only minimal maintenance, keeping them clean inside and out is usually all that is required. Heat transfer paste should be renewed if the sensor is removed for calibration or replacement.
46
© Burns Engineering Thermowell Selection and Application
Thermowell selectionMaterial selection
CorrosionErosionStrength
Process connection styleFlangeThreadedWeldedSanitary
Stem styleWake frequency and strength calculationsImmersion lengthSurface finishTime response
Thermowell Selection Checklist
47
© Burns Engineering Thermowell Selection and Application
Thermowell basicsPurposeTypesProcess connection stylesMaterials, coatings and surface finish
PerformanceWake frequency & strengthImmersion lengthTime response
Custom designsSpecifying
Definitions/codesTypical drawingDetailsTesting & certificationsOptions
Preventive Maintenance Selection Checklist
Summary
© Burns Engineering Thermowell Selection and Application
Questions?Use the chat window to send us a question now
Contact us later at 800-328-3871 or visit www.burnsengineering.com
Thank you for attending!
© Burns Engineering Thermowell Selection and Application
BE educated
Watch for upcoming RTDology™ events
Q & A revisitedYour idea? Let us know what topic you would like coveredView recordings and slides from previous sessions on our website at: www.burnsengineering.com/RTDology