Commissioning Report Gas ~ Hoval .... Engineer P.Hepworth SAP Job
Number 75019279 Date 3' August 2105 Functional Location 1389466
Site Address Genfell Tower 601815101415
Grenfell Road ment Number 12272040 London W11 1 TQ Firin Control
Number 1443H8516
Boiler Manufacture Hoval Burner Manufacturer Fuel Natural Gas I
Boiler Model Ultra Gas Model Type Burner Modulating Rated kW Select
200 Serial Number
Commission in-line with Hoval Specification Work
Production Year 2015
Ambient oc 29.5 Temperature
Gas Head Pressure m bar
Gas Rate Select
Combustion m bar
Fan Speed RPM 3900
Hours Run Hours 0
Number of Starts 3
Number procedure
The heat1ng system water quality should sat1sfy the standards as
detailed 1n the Hoval Technical and Installation Instruction Manual
supplied with the appliance
Low High Low Flame Flame Flame Appliance Safety Checks Gas Oil
Oil
8.73 I 314 Inch Automatic Air
Safety Valve I 3_2 bar Vent fitted
5.6 Type of interlock control Enable (VE 1) & safety (B5)
1 Thermostat I Control oc High Limit oc Settings HiQh!low oc
ModulatinQ oc
0.0000 Safety controls and interlocks tested Yes Dry Run Check
Yes
45 System Safety Checks
Ventilation. (We assume that the ventilation takes in 43.6 to
account summer use, as required by the British
Standards)
98.5 Does the appliance share the fuel supply?
89.2 Fuel system type
25.7 Type of flue System
Is the flue system/installation correct and functional? Has a flue
flow and/or spillage test been completed?
Is the smoke box trap fitted and piped to drain?
Is the flue terminal fitted in line with the Hoval
instructions?
-0.133 Findings
900 Has the appliance been installed to the relevant standards and
manufacturer's instructions?
Is the appliance safe to use?
If the appliance is not safe to use, how has it been classified?
Has a warning notice been raised and label attached to the
appliance? Has the appliance been disconnected from the fuel
supply?
Is further work required?
Yes
Yes
Yes
Main
Yes
Shared
Yes
N/A
Yes
Yes
Yes
Yes
N/A
N/A
N/A
No
Commission lAW Hoval Procedures. See Report for site specific
details, defects and recommendations.
Hoval Limited, Northgate, Newark, Notts.NG24 1 JN. Tel ax:~~·
Web: www.hoval.co.uk E-mail:
[email protected]
SC.P 15 Rev 00
------------------------------------------------------------------
Commissioning Report Gas ~ Hoval .... Engineer P.Hepworth SAP Job
Number 75019279 Date 3' August 2105 Functional Location 1389466
Site Address Grenfell Tower 601815101421
Grenfell Road ment Number 12272046 London W11 1 TQ Firin Control
Number 1434H3336
Boiler Manufacture Hoval Burner Manufacturer Fuel Natural Gas I
Boiler Model Ultra Gas Model Type Burner Modulating Rated kW Select
200 Serial Number
Commission in-line with Hoval Specification Work
Production Year 2015
Ambient oc 23.3 Temperature
Gas Head Pressure m bar
Gas Rate Select
Combustion m bar
Fan Speed RPM 3900
Hours Run Hours 0
Number of Starts 3
Number procedure
The heat1ng system water quality should sat1sfy the standards as
detailed 1n the Hoval Technical and Installation Instruction Manual
supplied with the appliance
Low High Low Flame Flame Flame Appliance Safety Checks Gas Oil
Oil
8.64 I% Inch Automatic Air Safety Valve I 3_2 bar Vent fitted
5.8 Type of interlock control Enable (VE 1) & safety (B5)
2 Thermostat I Control oc High Limit oc Settings HiQh!low oc
ModulatinQ oc
0.0000 Safety controls and interlocks tested Yes Dry Run Check
Yes
56 System Safety Checks
Ventilation. (We assume that the ventilation takes in 42.2 to
account summer use, as required by the British
Standards)
98.3 Does the appliance share the fuel supply?
89.1 Fuel system type
24.8 Type of flue System
Is the flue system/installation correct and functional? Has a flue
flow and/or spillage test been completed?
Is the smoke box trap fitted and piped to drain?
Is the flue terminal fitted in line with the Hoval
instructions?
-0.535 Findings
900 Has the appliance been installed to the relevant standards and
manufacturer's instructions?
Is the appliance safe to use?
If the appliance is not safe to use, how has it been classified?
Has a warning notice been raised and label attached to the
appliance? Has the appliance been disconnected from the fuel
supply?
Is further work required?
Yes
Yes
Yes
Main
Yes
Shared
Yes
N/A
Yes
Yes
Yes
Yes
N/A
N/A
N/A
No
Commission lAW Hoval Procedures. See Report for site specific
details, defects and recommendations.
Hoval Limited, Northgate, Newark, Notts.NG24 1 JN. Tei-Fax-
Web: www. ova .co.u -ma1: service~o.uk
SC.P 15 Rev 00
------------------------------------------------------------------
Commissioning Report Gas ~ Hoval .... Engineer P.Hepworth SAP Job
Number 75019279 Date 3' August 2105 Functional Location 1389466
Site Address Grenfell Tower 601815101427
Grenfell Road ment Number 12272052 London W11 1 TQ Firin Control
Number 1434H3330
Boiler Manufacture Hoval Burner Manufacturer Fuel Natural Gas I
Boiler Model Ultra Gas Model Type Burner Modulating Rated kW Select
200 Serial Number
Commission in-line with Hoval Specification Work
Production Year 2015
Ambient oc 20.7 Temperature
Gas Head Pressure m bar
Gas Rate Select
Combustion m bar
Fan Speed RPM 3900
Hours Run Hours 0
Number of Starts 3
Number procedure
The heat1ng system water quality should sat1sfy the standards as
detailed 1n the Hoval Technical and Installation Instruction Manual
supplied with the appliance
Low High Low Flame Flame Flame Appliance Safety Checks Gas Oil
Oil
8.69 I 314 Inch Automatic Air
Safety Valve I 3_2 bar Vent fitted
5.7 Type of interlock control Enable (VE 1) & safety (B5)
1 Thermostat I Control oc High Limit oc Settings HiQh!low oc
ModulatinQ oc
0.0000 Safety controls and interlocks tested Yes Dry Run Check
Yes
43 System Safety Checks
Ventilation. (We assume that the ventilation takes in 42.5 to
account summer use, as required by the British
Standards)
98.1 Does the appliance share the fuel supply?
88.9 Fuel system type
24.8 Type of flue System
Is the flue system/installation correct and functional? Has a flue
flow and/or spillage test been completed?
Is the smoke box trap fitted and piped to drain?
Is the flue terminal fitted in line with the Hoval
instructions?
-0.566 Findings
900 Has the appliance been installed to the relevant standards and
manufacturer's instructions?
Is the appliance safe to use?
If the appliance is not safe to use, how has it been classified?
Has a warning notice been raised and label attached to the
appliance? Has the appliance been disconnected from the fuel
supply?
Is further work required?
Yes
Yes
Yes
Main
Yes
Shared
Yes
N/A
Yes
Yes
Yes
Yes
N/A
N/A
N/A
No
Commission lAW Hoval Procedures. See Report for site specific
details, defects and recommendations.
SC.P 15 Rev 00
18'" September 2105 1389466 Date Functional Location
Grenfell Tower Grenfell Road Appliance Serial Number See
Table
Site Address London W11 1 TQ Equipment Number See Table
Firing Control Number See Table
Appliance Model Hoval UltraGas Burner Manufacturer NA
Burner Type Modulating Model Type NA
Rated Output kW 200 Serial Number NA
Production Year 2015
Specification Number NA
Additional Appliances if required
Appliance Equipment K Number Serial Fire Control No Of Starts Hour
Run Number Number Number Number Serial Number
Boiler 1 12272052 601815101427 1443H3330 3 0
Boiler 2 12272040 601815101415 1443H8516 3 0
Boiler 3 12272046 601815101421 1443H3336 22 11
Comments:
Attend site to commission 3 x UtraGas boilers
Following site induction liaised with site contact and proceeded to
plant room.
AA Vs and PR Vs fitted to all boilers. No flue test points fitted
(installer drilled test holes into single skin part of the flue).
Boilers have traps fitted as supplied.
Ventilation ductwork incomplete however for commissioning purposes
the is sufficient supply and extract ventilation. Interlocks have
been fitted to supply and extract fans. Interlocks are wired to
disable main gas solenoid is de-energised and all enable signals
are cut. Safety circuit through the boilers will be operate in the
event of the fire alarm.
Plant room is also incomplete and is likely to change before job
completion.
Combustion and gas pressures checked and details recorded on
combustion sheets for each boiler.
Another visit will be required once the ventilation and controls
are complete.
NB . As the plant room, ductwork, interlocks to supply and extracts
are not as they will be at completion the commissioning
certificates only cover the plant room and ventilation in its
current state . A!:r£ changes to the above will invalidate the
commissioning certificates and Hoval will need to return to ensure
changes meet relevant standards and safety requirements.
*lt would also be worth considering re-routing the supply
ventilation ducting to more evenly distribute the supply air across
the plant room.
Findings Parts used
P/No Part Required
P/No (description) (description) Has the appliance been installed
to the relevant
Yes standards and manufacturer's instructions?
Is the appliance safe to use? Yes
If the appliance is not safe to use, how has it N/A
been classified? Has a warning notice been raised and label
N/A attached to the appliance? Has the appliance been disconnected
from the
N/A fuel supply?
Is further work required? No
PLEASE TAKE SPECIAL NOTE:- The heating system water quality should
be in accordance with Hoval's requirements as detailed in the
Technical and Installation Manual supplied with the
boiler(s).
P.Hepworth
Web: www.hoval.co.uk E-mail:
[email protected]
SC.P 18 Rev 00