Hoval AgroLyt® (20-50)Log Wood Boiler
Subject to alterations, 1.8.2013 3
Hoval AgroLyt®
Heating boiler
steel boiler in compliance with EN 303-5
for burning split wood, chippings or wood
briquettes
can be combined with separate energy
storage unit
integrated safety heat exchanger for thermal
process control
-
haust and air-cooled lining
be adjusted
vortex combustion chamber with pre-heating
ducts and heat-proof ceramic inlet jets for
the secondary air intake
thermolytic secondary heating surfaces
and auxiliary switch for automatic low-tem-
pe rature gas exhaust system
kindling and ash door placed above grate
ash removal door for simultaneous access to
combustion chamber
options (delivered from factory):
- with or without mechanical aid to clear
and comfort WiKo (separately packed)
- with boiler control panel N5.1
(separately packed)
boiler door swivel-mounted to the left
thermal insulation with 80 mm mineral wool
matting (sep. packed)
lining made of powder coated sheet steel
(sep. packed)
suction ventilator with automatic low-tempe-
rature gas exhaust, load dependent
(ready wired and separately packed)
Accessories (included with delivery)
soot brush, ash scraper, poker and stand
Delivery
boiler, thermal insulation and casing plus
boiler control panel and if required surface
clearing aid delivered separately packed
On site
installation of the thermal insulation and
casing of the heating boiler
Installation
boiler control panel
WiKo aid for clearing heating surface
(only with WiKo version)
Plant test
plant test and demonstration (obligatory)
Boiler control panel N5.1
boiler control panel for mounting on boiler
or laterally to the left or right
prepared for installation of a TopTronic®T
heating controller
Basic boiler control with:
main switch ‘I/O’,
boiler temperature display
boiler temperature controller for two-stage
operation
boil er minimum temperature monitor for boil-
er start-up protection
fan
connector for door contact safety switch
connector for suction ventilator
connector for buffer charging pump
E connector 230 V, 50 Hz
WiKo clearing aid for Hoval AgroLyt®
mechanical aid to clear heating surface for im-
Model series
AgroLyt® Heating capacity
Type kW
(20) 20
(25) 25
(35) 35
(50) 50
Return temperature control group
type RH 32-TK (thermal)only for AgroLyt® with boiler control N5.1
consisting of:
with cable ready for connection to boiler con-
trol N5.1.
3 shut off switch ball valves:
- storage tank-return
-
- boiler return with thermometer
® sizes.
Delivery
return temperature control group and stora-
ge tank loading pump with cable supplied in
se parate packaging.
On site
installation of the prepared return tempera-
ture control group on boiler
mounting of biral pump
Energy storage unit EnerValHot water storage tank with large lower flange
for heating, electrical ignition cartridge and
thermostats and thermometer.
operating pressure: max. 3 bar
operating temperature: max. 95 °C
As required:
thermal insulation for energy storage unit.
Approval heating boiler
AgroLyt® (20-50)
VKF No. 13369
VHe No. / HeS No. 0022/3
Description
4 Subject to alterations, 1.8.2013
Hoval AgroLyt® (20-50)Log Wood Boiler
Heating regulator set ZN2As supplement to boiler control N5.1.
Consisting of:
heating regulator Hoval TopTronic®T/N for
- 1 mixing circuit
- hot water charging circuit
possibility of further functions using various
key modules
large LCD display
turn-and-press button
keys for
- day room temperature
- night room temperature
- hot water temperature
- operating mode (holiday, absence,
heating period extension, automatic,
summer, heating period permanent –
reduced – frost protection)
- characteristic curve setting
- plant information
- emission measurement
and manual operation
outdoor sensor AF200
connection for room controls
cable set
for connecting the heating regulation
TopTronic®T/N to the boiler control
Delivery
heating regulator set separately packed,
installation on site
Part N°
Part N°
Hoval AgroLyt® (20-50)
Subject to alterations, 1.8.2013 5
7007 091
7007 092
7007 094
7007 098
AgroLyt® capacity length length volume
type kW m mm litres
(20) 20 ½ 570 140
(25) 25 ½ 570 160
(35) 35 ½ 570 160
(50) 50 ½ 570 220
Steel boiler with basic boiler control. Integrated
safety heat exchanger for thermal process
con trol.
Boiler, boiler control panel and thermal insulati-
on with lining delivered separately packed.
Log wood boiler Hoval AgroLyt®
with basic boiler control N5.1
7007 101
7007 102
7007 104
7007 108
AgroLyt® capacity length length volume
type kW m mm litres
(20) 20 ½ 570 140
(25) 25 ½ 570 160
(35) 35 ½ 570 160
(50) 50 ½ 570 220
As described above, but including heating
surface clearing aid WiKo.
Boiler, boiler control panel, heating surface
clearing aid and thermal insulation material
with cladding supplied separately.
Log wood boiler Hoval AgroLyt® with
basic boiler control N5.1 and heating
surface clearing aid WiKo
CAUTION:
It is essential to install
a return temperature control!
It is essential to install an energy-saving
draught restrictor ZT 15!
See the notes under required draught
and chimney
by about 35 °C by use of the heating
surface clearing device!
Lambda probe
for AgroLyt® (20-50)
with boiler controller
N5.2/TopTronic® lambda
for combustion optimisation
incl. assembly accessories
6915 80
Part N°
Part N°
6 Subject to alterations, 1.8.2013
Hoval AgroLyt® (20-50)
7007 111 7007 112
7007 114
7007 115
7007 118
7007 121
7007 122
7007 123
7007 124
7007 125 7007 128
Nominal Log Filling capacity
AgroLyt capacity length length volume
type kW m mm litres
(20) TTL 18,0 1/2 570 140
(25) TTL 25,0 1/2 570 160
(30) TTL 27,2 1/2 570 160
(35) TTL 36,0 1/2 570 160
(40) TTL 39,7 1/2 570 160
(50) TTL 50,0 1/2 570 220
Configuration as on the previous page, but
additionally with heating surface cleaning
WiKo.
Delivery: Boiler, boiler switch panel and ther-
mal insulation with cladding and heating sur-
face cleaning are supplied separately packed.
Log wood boiler Hoval AgroLyt® with basic
boiler control N5.2 TopTronic® lambda and
heating surface clearing aid WiKo
Nominal Log Filling capacity
AgroLyt capacity length length volume
type kW m mm litres
(20) TTL 18,0 1/2 570 140
(25) TTL 25,0 1/2 570 160
(35) TTL 36,0 1/2 570 160
(40) TTL 39,7 1/2 570 160
(50) TTL 50,0 1/2 570 220
but with boiler control N5.2/TopTronic® lambda.
tact sensor and energy buffer storage sensor
for combustion and performance optimisation.
Delivery: Boiler, boiler switch panel and ther-
mal insulation with cladding are supplied sepa-
rately packed.
Lambda probe for optimising combustion
and return temperature control group type
RH32-M must be ordered separately (see
accessories).
Log wood boiler Hoval AgroLyt®
with basic boiler control N5.2/
TopTronic® lambda
CAUTION:
It is essential to install a
return temperature control!
It is essential to install an energy-saving
draught restrictor ZT 15!
See the notes under required draught
and chimney
CAUTION: load is reduced by approx. 35 °C on average by the heating surface cleaning!
CAUTION:
It is essential to install a
return temperature control!
It is essential to install an energy-saving
draught restrictor ZT 15!
See the notes under required draught
and chimney
Ash-tray
for AgroLyt®
Consisting of:
Upper and lower ash-trays, including
wall bracket and fixing material.
6412 60
Wood chip chute
for AgroLyt® (20-50)
for easier filling with wood chips
and kindling.
The proportion of wood chips or kindling
should not exceed 50% of a wood load.
Proper combustion is only to be ensured
with a correct mixture of at least 50%
log wood (½-metre).
6024 343
Thermal return temperature control group
type RH 32-TK
for AgroLyt® (20-50)
suitable for boiler control panel N5.1:
Thermal control valve
3-way valve and high-efficiency pump
6022 624
Return temperature control kit DN25
for BioLyt (15,23), AgroLyt® (20,25)
for return flow temperature increase
Consisting of:
3-way motor mixer
kvs: 12 m3/h
6032 419
Return temperature control kit DN32
for BioLyt (25-36), AgroLyt® (35,50)
for return flow temperature increase
Consisting of:
3-way motor mixer
kvs: 18 m3/h
6027 843
Part N°
Part N°
Hoval AgroLyt® (20-50)
Subject to alterations, 1.8.2013 7
Boiler accessories
6032 418
6022 628
for AgroLyt® (20,25) Mixer: kvs 12 m3/h
for AgroLyt® (35,50) Mixer: kvs 18 m3/h
Return temperature control group DN32
for return flow temperature increase
With 3-way motor mixer and Biral pump
Ball valves in installation flow/return
Valve equipped with thermometer
in boiler return
Insulated piping
Complete with fittings for
assembly at boiler connection
Connection: Rp 1¼"
Pump enclosed separately.
6027 955
6027 956
6027 957
Automatic ignition device
Consisting of:
hot air blower with electrical kit and
cover hood; incl. assembly accessories.
for AgroLyt® (20) TTL
for AgroLyt® (25-40) TTL
for AgroLyt® (50) TTL
Heating regulator set ZN2
as addition to boiler control panel N5.1
for the connection of the heating
regulator TopTronic®T/ N with the
boiler controller
Consisting of:
Heating regulator TopTronic®T/N for
- 1 mixer circuit
- 1 domestic hot water loading circuit
Outdoor sensor AF200
Flow sensor VF204
with 4 m cable
2 immersion sensors KVT20/5/6
for calorifier and buffer storage unit
with 5 m cable
Cable set ZN2
Delivery:
Heating regulator set separately packed,
mounting on-site
6020 567
Heating regulator set N2
as addition to boiler control panel
N5.2/ TopTronic® lambda
Consisting of:
Heating regulator TopTronic®T/N for
- 1 mixer circuit
- 1 domestic hot water loading circuit
Outdoor sensor AF200
Flow sensor VF204
with 4 m cable
2 immersion sensors KVT20/5/6
for calorifier and buffer storage unit
with 5 m cable
Delivery:
Heating regulator set separately packed,
mounting on-site
6020 569
Part N°
Part N°
8 Subject to alterations, 1.8.2013
Hoval AgroLyt® (20-50)
Heating regulator set TopTronic®T
Control set to be fitted into the boiler switch
panel on site.
Delivery
Heating control set packed separately
Part N°
Part N°
Hoval AgroLyt® (20-50)
Subject to alterations, 1.8.2013 9
Key module 1
for 2nd mixing circuit
function key 1, 1 flow sensor, 2 loose plugs
Key module 2
for solid fuel/ buffer storage unit/ bivalent plant
function key 2, 3 immersion sensor, 4 loose plugs
Key module 3
for solar plants
function key 3, 1 collector sensor, 1 storage
sensor, 4 loose plugs
Key module 4
for 2nd mixing circuit and solid fuel/ buffer storage
unit/ bivalent plant
function key 4, 1 flow sensor, 3 immersion sensor,
6 loose plugs
Key module 5
for 2nd mixing circuit and solar plant
function key 5, 1 flow sensor, 1 collector sensor,
1 storage sensor, 6 loose plugs
Key module 6
for solid fuel/buffer storage unit/bivalent plant and
solar plant
function key 6, 1 collector sensor, 4 immersion
sensor, 6 loose plugs
Key module 7
for 2nd mixing circuit, solid fuel/buffer storage unit/
bivalent and solar plant
function key 7, 1 flow sensor, 1 collector sensor,
4 immersion sensor, 8 loose plugs
Sensor types
Immersion-/ : Typ KVT20/5/6 (L = 5 m)
calorifier sensor without immersion sleeve
Flow sensor : Type VF204S with plug
Collector sensor : Type PT1000 (Silicon)
Accessories for heating regulation
system TopTronic®T
M
Key Modules for TopTronic®T
for further functions in addition
to the standard functions.
Key module consisting of:
function key for insertion into the
TopTronic®T incl. fittings
Only one key module possible!
6012 154
6012 155
6012 156
6012 157
6012 158
6012 159
6012 160
Standard functions
already realised in the TopTronic®T.
- 1 mixing circuit
- hot water charging circuit
1
2
3
4
5
6
7
1-7
M
M
M
M
M
M
3
Functions of the key modules
key 2nd mixing solid buffer solar
module circuit bivalent
2
1
4
5
6
7
M
System Solutions and Applications
see Hoval CD
Room station RS-T
for TopTronic®T
effective on one mixing circuit
2034 939
Remote control RFF-T
for TopTronic®T
effective on one mixing circuit
2022 239
Outdoor sensor AF 200
(may be included in the heat generator
scope of delivery)
for one mixing circuit or for the mean
value (per regulator 2 outdoor
temperature sensors possible)
2022 995
Cable sensor KVT 20/5/6
with 5 m cable
2022 992
Contact sensor VF204
can be used as flow or return
flow sensor
with 4 m cable
2023 998
Flue gas thermometer with drag indicator
Ø 5 / 80x150 mm (mounting on site)
Range of indication 100°C - 500°C
2412 37
Flow temperature guard
RAK-TW1000.S SB 280
Range of switching temperatures
adjustable with tools 15-95°C
switching differential 6K
Thermostat with immersion sleeve ½"
depth of immersion 280 mm
brass nickel-plated
6010 083
Part N°
Part N°
10 Subject to alterations, 1.8.2013
Hoval AgroLyt® (20-50)
Accessories for heating regulation
system TopTronic®T
Flow temperature guard
for floor heating system (heating circuit
1 guard) 15-95 °C, differential gab 6 K, capilla-
ry tube max. 700 mm setting (visible from the
out side) inside the housing cover
Clamp-on thermostat RAK-TW1000.S
Thermostat with strap, without cable and plug
242 902
Immersion thermostat RAK-TW1000.S SB 150
Thermostat with pocket ½" - depth of immersi-
on 150 mm, brass nickel-plated
6010 082
Flue gas thermostat AGT 519
Switching temperature 80 °C
(switching differential approx. 15 K)
1 switchover contact 10 A
at 230 V/ 50 Hz ohm resistive load
Simple screw fastening on flue pipe,
with 2 m connecting cable.
Tested according to DIN 3440
6412 56
Damper ZT 15
Damper Z130 and T-piece 90° of
stainless steel
Inner Ø 150 mm
6008 037
Thermal process control unit STS20
Valve ¾" with capillary tube 1,3 m
Immersion well ½", L 142 mm
2426 62
Safety set SG15-1"
Suitable up to max. 50 kW
complete with safety valve (3 bar)
Pressure gauge and automatic air vent
with cut off valve
Connection: 1" internal thread
6411 84
Thermal control valve
for return flow temperature
increase 57 °C
1½"
incl. integrated check valve
kVS = 14
6409 29
Three way valve B3G460
PN 10, 110°C, DN 32
case, shaft and segment made of brass
maintenance-free O-ring seal
Mounting optionally on left or
right side
kvs value 18 m3/h
2039 170
Actuator NR230-E-20
for three-way valve B3G460
Operating voltage 230V/50Hz
Single wire control
Torque 10 Nm
Actuation time 140 s
manual/automatic positioning
reversible direction of rotation and
scale for position indicator 0...10
1 cable (2 m) for actuator mounted
on the drive.
Complete with assembly material
2452 35
Part N°
Part N°
Hoval AgroLyt® (20-50)
Subject to alterations, 1.8.2013 11
Accessories
Further information
see separate brochure
Switchover unit: For alternating operation of
a solid fuel boiler with a boiler of a different
energy type or for start-up relief
Technical data
12 Subject to alterations, 1.8.2013
Hoval AgroLyt® (20-50)
Hoval AgroLyt® with basic boiler control N5.1
Type (20) (25) (35) (50)
Hoval AgroLyt® N5.1
nominal heating capacity (N5.1) kW 20 25 35 50
heating capacity range (N5.1) kW 16-20 19-25 26-35 35-50
Data for deciduous wood
usable heating value (tolerance ± 20 %) kWh 180 200 200 265
kg 47 53 53 70
combustion time at nominal heating capacity approx. h 7,8 6,8 4,9 4,5
log length m ½ ½ ½ ½
Data for coniferous wood
usable heating value (tolerance ± 20 %) kWh 126 140 140 179
kg 35 39 39 50
combustion time at nominal heating capacity approx. h 5,4 4,9 3,5 3,2
log length m ½ ½ ½ ½
maximum heating boiler operating temperature °C 85 85 85 85
minimum heating boiler operating temperature °C 70 70 70 70 °C 55 55 55 55
1 at nominal capacity without WiKo °C 190 190 200 2001 at nominal capacity with WiKo °C 160 160 160 170
carbon dioxide CO2
% 10-14 10-14 10-14 10-14
operating pressure / testing pressure bar 3,0/4,5 3,0/4,5 3,0/4,5 3,0/4,5
80 °C boiler water temperature (N5.1) % >88 >88 >88 >88
11,0 % CO2, humidity content of wood 20 % kg/h 64 76 105 144
throughput resistance wood boiler z-value 2,8 2,8 2,8 2,7
water side resistance at 10 K mbar 8,3 12,9 25,2 50,2
water side resistance at 20 K mbar 2,0 3,2 6,3 12,5
water throughput at 10 K m3/h 1,72 2,15 3,01 4,30
water throughput at 20 K m3/h 0,86 1,07 1,50 2,15
boiler water content litres 195 195 190 220
litres 140 160 160 220
thickness of boiler body insulation mm 80 80 80 80
weight with casing kg 750 750 760 835
without casing kg 680 680 690 745
width mm 350 400 400 400
height mm 620 620 620 840
depth mm 570 570 570 570
feeding aperture width x height mm 450x400 450x400 450x400 450x400
dimensions (with/without switch panel) width mm 860/690 860/690 860/690 860/690
(with/without switch panel) depth mm 1375 1375 1375 1375
height mm 1670/1500 1670/1500 1670/1500 1890/1720
dimensions for installation width mm 600 600 600 600
depth mm 1200 1200 1200 1200
height mm 1570 1570 1570 1790
Thermal process control
switching point for the thermal process control °C 95 95 95 95
minimum throughput water quantity (cold water 10 °C) m3/h 1,50 1,5 2,0 2,0
bar 2,0/6,0 2,0/6,0 2,0/6,0 2,0/6,0
Flue gas system 1
minimum draught required for boiler Pa 10 10 10 10
maximum permitted draught Pa 25 25 25 25
nominal electrical power requirement (N5.1) watts 80 80 80 80
1 A damper control must be installed.
Dimensions
Hoval AgroLyt® (20-50)
Subject to alterations, 1.8.2013 13
(Dimensions in mm)
AgroLyt® Height
Type H1 H2 A C D
(20-40) 1500 1570 1544 1335 1236
(50) 1720 1790 1764 1555 1456
* Required space
Boiler control can be mounted
on top or on left or right side
1a Boiler flow connection R 1¼"
1b Installation flow connection Rp 1¼"
2a Boiler return connection R 1¼"
2b Installation return connection Rp 1¼"
3 safety heat exchanger 2 x R ½"
4 connector safety group and air vent, Rp 1"
5 drainage R ¾"
6 flue gas sleeve Ø150 (outer)
Space requirements
– see separate drawing
Heig
ht H
1
Heig
ht H
2 *
7 immersion well for boiler water
temperature sensor
8 sleeve for safety heat exchanger sensor Rp ½"
9 suction ventilator
10 electrical controls
11 aperture for cleaning
12 heating surface clearing aid Wiko
Dimensions
14 Subject to alterations, 1.8.2013
Hoval AgroLyt® (20-50)
Space requirements
(Dimensions in mm)
Space requirements for
mounting the side casing.
After mounting the casing
the boiler can be moved
against the wall.
Minimum lateral space
requirements incl. control
panel, for servicing the
safeguard
appro
x. 700
min 1200
min 600min 400
min 400
Minimum spacing 700 mm.
The cleaning aperture at
the boiler must be easy to
access.
Engineering
Hoval AgroLyt® (20-50)
Subject to alterations, 1.8.2013 15
Maximal filling quantity based on VDI 2035
[mol/m3] 1 <0,1 0,5 1 1,5 2 2,5 3 >3,0
f°H <1 5 10 15 20 25 30 >30
d°H <0,56 2,8 5,6 8,4 11,2 14,0 16,8 >16,8
e°H <0,71 3,6 7,1 10,7 14,2 17,8 21,3 >21,3
~mg/l <10 50,0 100,0 150,0 200,0 250,0 300,0 >300
Conductance 2 <20 100,0 200,0 300,0 400,0 500,0 600,0 >600
Boiler size of
individual boiler
to 50 kW NO REQUIREMENT 20 l/kW
1 sum of alkaline earths2 If the conductance in µS/cm exceeds the tabular value, a water analysis is necessary.
Regulations and GuidelinesThe following regulations and guidelines
must be observed:
Hoval’s technical information and installation instructions.
Hoval’s hydraulic and technical control regulations.
Local building law
Fire protection standard
DVGW guidelines
DIN EN 12828 Heating systems in buildings
- Design of hot water systems.
DIN EN 12831 Heating systems in buildings - Procedure for calculation of the standard heating capacity
VDE 0100
Water qualityHeating water
The European Standard EN 14868 and the Directive VDI 2035 must be observed.
Hoval boilers and calorifiers are designed for heating plants without significant oxygen intake (plant type I according to EN 14868).
Plants with
- continuous oxygen intake
(e.g. underfloor heating systems without
diffusion proof plastic piping) or
- intermittent oxygen intake
(e.g. where frequent refilling is necessary)
must be equipped with separate circuits.
Treated heating water must be tested at
least 1 x yearly. According to the inhibitor
manufacturer‘s instructions, more frequent
testing may be necessary.
A refilling is not necessary if the quality of
the heating water in existing installations
(e.g. exchange of boiler) conforms to
VDI 2035. The Directive VDI 2035 applies
equally to the replacement water.
New and if applicable existing installations
need to be adequately cleaned and flushed
before being filled. The boiler may only be
fil led after the heating system has been
flush ed!
Parts of the boiler which are in contact with
water are made of ferrous materials.
On account of the danger of stress cracking
corrosion the chloride, nitrate and sulphate
contents of the heating water must not ex-
ceed 200 mg/l in total.
The pH value of the heating water should
lie between 8,3 and 9,5 after 6 -12 weeks of
heating operation.
Filling and replacement water:
For a plant using Hoval boilers untreated
drink ing water is generally best suited as
heat ing medium, i.e. as filling and replace-
ment water. However, the quality of the
un treat ed drinking water must fulfil the
stand ard set in VDI 2035. Should the mains
wa ter available not be suited for use then it
must be desalinated and/ or be treated with
in hibitors. The stipulations of EN 14868 must
be observed.
In order to maintain a high level of boiler
ef fi ciency and to avoid overheating of the
heat ing surfaces the values given in the
ta ble should not be exceeded (dependent on
boil er performance ratings - for multi-boiler
plants rating of smallest boiler applies - and
on the water content of the plant).
The total amount of filling and replacement
water which is used throughout the total ser-
vice life of the boiler must not exceed three
times the water capacity of the plant.
Boiler roomThe boiler room must comply with fire regu-lations.
The combustion air supply must be guaran-
teed. The air opening should be in the lee
of the prevailing wind direction and may not
be shuttered in any way. The minimum free
opening cross-section is 200 cm2.
Space requirements
-
sible (for the purpose of dismantling it).
Buffer Storage Unit SelectionRecommended minimum storage unit size
AgroLyt® storage unit volume *
type minimum dm3
(20) 1000
(25) 1500
(35) 2000
(50) 3000
out side temperature maximum 40°C, heating
quan tity is taken up by the storage unit.
Engineering
16 Subject to alterations, 1.8.2013
Hoval AgroLyt® (20-50)
Installation
Buffer storage unit and
return flow safeguard
For the Hoval AgroLyt® a buffer storage unit
with automatic storage and charging con trol
and boiler return flow control must be in stal-
led.
Hydraulic switching
Please observe the examples for use.
Heat distribution
For central heating of rooms an automatic
temperature regulator with one or more mix-
ing circuits should be installed.
Plant with open expansion chamber
The height of the plant must be such that at
least the required minimum pressure in the
suction pipe of the pump is maintained in
order to prevent cavitation
(see heading ‘circulation pumps - pumps’)
Plant with pressurised expansion chamber
In accordance with the SWKI regulation 93-1
pressurised expansion chambers are only
permissible in combination with a thermal
process controller consisting of an integrated
heat exchanger in the boiler together with a
thermal discharge valve.
Safety valve
A safety valve with an automatic air vent
must be installed at the connector for the
safety group.
Thermal Process ControlIf a pressurised expansion chamber is in stal-
led then a thermal process controller must
also be installed
(in accordance with. SWKI regulation 93-1).
The thermal process control must be con-
nec ted to the cold water supply. The mini-
mum required flow pressure is 2 bar.
Minimum throughput:
AgroLyt® (20) = 1500 l/h
(25) = 1500 l/h
(35) = 2000 l/h
(50) = 2000 l/h.
The cleaning aperture for the connector (top
of boiler) must remain easily accessible. In-
stall water pipes vertically upwards.
Boiler Selection
the hourly heating capacity demand of the
building.
how often the boiler must be fuelled so that
the heating demand is covered in periods of
minimum outside temperatures.
Qh = Heating requirement at -10 °C
outside temperature
°C = The daily heating requirement can be met when
at least this outside temperature prevails.
Basis for calculation: Firing with deciduous wood,
= 14 x Qh.
type (20) type (25) type (35) type (50)
loads/day loads/day loads/day loads/day
Qh 1 2 1 2 1 2 1 2
kW °C °C °C °C °C °C °C °C
6 – –
8 -10 – –
10 -10 -10 -10
12 -5 -10 -9 - 9 - 10
14 -2 -10 -5 -5 - 10
16 1 -10 -1 -1 - 8
18 3 -10 1 -10 1 -10 - 5
20 5 -10 3 -10 3 -10 - 2
25 – – 6 -8 6 -8 2 - 10
30 – – 9 -2 5 - 10
35 – – 10 0 7 - 5
40 9 - 3
45 9 0
50 11 2
Engineering
Hoval AgroLyt® (20-50)
Subject to alterations, 1.8.2013 17
Chimney
The Agrolyt® must be connected to a chim-
ney (flue gas temperature > 200 °C).
The effective height of the chimney must be
at least 6 m.
The chimney outlet should be higher than
the roof ridge.
The flue gas ducts must be capable of with-
standing humidity, acidity and soot combus-
tion and be approved for flue gas tempera-
tures > 160 °C.
Existing chimneys must be renovated ac-
cord ing to the instructions of a chimney
con structor.
Determination of the flue gas duct cross-
section in accordance with EN 13384
Part 1 and 2
A flue gas thermometer (included with the
AgroLyt®) must be installed in the connec-
ting pipe. This is necessary in order to main-
tain a high level of plant efficiency.
An auxiliary air flap as chimney damper con-
trol is recommended.
Non-binding standard values
for chimney cross-sections
made of chrome steel piping connecting pipe
= 1,0. connecting pipe and heating boiler
connecting pipe and chimney should be ther-
mally insulated. Height above sea level
AgroLyt®
type (20) (25) (35) (50)
m Ø (mm)
11-15 175 175 175 200
6-10 175 200 200 225
m = effective chimney height
Ø = minimum required chimney diameter (mm)
Chimney / Flue SystemConnecting pipe
Feed the flue pipe connecting increasing
bet ween the heating boiler and the chimney
with a gradient of 30-45° into the chimney, if
possible.
For a pipe longer than 1 m thermal insulation
is necessary.
The connecting pipe must be introduced into
the chimney in such a way that no conden-
sate can flow into the heating boiler.
The connecting pipe must contain a circular,
closable flue gas measurement aperture
with an inner diameter of 10-21 mm. The
ap er ture must be accessible through the
ther mal insulation if present.
Position:
D
D
2xD2D
1D
Required draught
In calculating the chimney dimensions the
chimney draught should be between 0,1
and 0,25 mbar (10-25 Pa).
To reliably prevent the occurrence of exces-sive flue draught, it is essential to install a damper. The damper ensures a constant flue draught, protection of the heating equip-ment, effective ventilation of the flue and optimum energy utilisation. This is the only reliable way to protect the boiler against ac-cidental overload.
Fuelair-dried, untreated log wood such as split
logs, billets or roundwood.
max. Ø 15 cm
guidelines for dry storage:
softwood 1 to 1½ years
hardwood 2 to 2½ years
untreated coarse wood chips
(humidity < 30 %) including attached bark
split wood (thus the proportion of coarse
chips can be approx. 50 % according to
quality).
Pressed chips, shavings etc with diameter
the use of bonding agents, in combination
with 50 % split wood (thus the proportion of
pressed wood can be approx. 50 % accord-
ing to quality).
Carpentry waste in the form of bonded wood
providing this is free from wood protection
50 % split wood (thus the proportion of car-
pentry waste can be approx. 50 % according
to quality).
Fuels
which may not be used
- coke, coal
- sawdust
- plastic-coated waste wood
- treated or painted wood
- plastic
- waste
The burning of waste, of wood treated with
wood preservatives or with a coating consi-
sting of halogenated organic compounds is
prohibited.
Please observe the 1. BImSchV (first regu-
lation for the implementation of the Federal
immission control law) § 6.
Determining the approx. yearly fuel demand
for central heating
wood requirement kg kW x 500
loose deciduous wood kW x 1
loose coniferous wood kW x 1,5
kW = max. heating demand in kW
kg, m3 = approx. yearly wood consumption
(note that the weight per m3 can
vary a great deal according to the
wood quality).
Examples
18 Subject to alterations, 1.8.2013
Hoval AgroLyt® (20-50)
Hoval AgroLyt® with basic boiler control N5.1
Monovalent plant with distributor and charging group, thermal return flow control,
2 energy storage units, 1 calorifier and 1 heating circuit
Hydraulic plan BDBT010
Monovalent plant with distributor and charging group, thermal return flow control,
2 energy storage units, 1 calorifier with solar plant and 1 heating circuit
Hydraulikschema BDBT060
RS-T Room station
AF Outdoor sensor
VF1 Flow sensor 1
VF2 Flow sensor 2
SF Calorifier heater sensor
B1 Flow temperature guard
(if required)
MK1 Pump mixing circuit 1
MK2 Pump mixing circuit 2
(optional)
M8 Buffer charging pump
PF Hot water tank sensor
SLP Calorifier loading pump
SOP Solar circulation pump
YK1 Actuator mixer 1
YK2 Actuator mixer 2
Y9 Switch over valve start up re-
lease (single wire system)
KRLF Solar panel return sensor
KSPF Solar tank sensor
(calorifier / buffer)
KVLF Solar panel flow sensor - PT1000
CW Cold Water
DHW Domestic Hot Water
DHW
CW
Notice:
- This hydraulic schematic is a principle
schematic. It does not contain all details
for installation. The installation must be
done according to local conditions, di men-
sioning and regulations
-
monitor must be built-in.
- Shut-off devices to the safety valve (pres-
surized expansion tank, safety valve, etc.)
are to safe against unintended closing!
- Mount bags to prevent single pipe gravity
circulation.
DHW
CW
Examples
Hoval AgroLyt® (20-50)
Subject to alterations, 1.8.2013 19
Bivalent plant with distributor and charging group, constant return flow control,
2 energy storage units, 1 calorifier and partial solar heating.
Hydraulic plan HDST030
Hoval AgroLyt® with boiler control N5.2/ TopTronic® lambda
Monovalent plant with distributor and charging group, constant return flow control,
2 energy storage units, 1 calorifier and 1 heating circuit
Hydraulic plan BDBT110
RS-T Room station
MK1 Pump mixing circuit 1
MK2 Pump mixing circuit 2
M8 Buffer charging pump
SLP Calorifier loading pump
SOP Solar circulation pump
SOP1 Solar circulation pump 1
SOP2 Solar circulation pump 2
SLV Water by-pass solar circuit
YK1 Actuator mixer 1
YK2 Actuator mixer 2
YKR Actuator return mixer
Y9 Switch over valve start up release
(single wire system)
B1 Flow temperature guard (if required)
SF Calorifier sensor
S1 Calorifier sensor
PF Buffer sensor
BP1 Buffer sensor 1
BP2 Buffer sensor 2
BRU Return sensor
AF Outdoor sensor
VF1 Flow sensor 1
VF2 Flow sensor 2
KSPF Solar tank sensor
(calorifier / buffer)
SLVF Solar sensor
(calorifier / buffer)
KVLF Solar sensor (collector PT1000)
S1-S5 Differential control sensor
CW Cold Water
DHW Domestic Hot Water
Notice:
- This hydraulic schematic is a principle
schematic. It does not contain all details
for installation. The installation must be
done according to local conditions, di men-
sioning and regulations
-
monitor must be built-in.
- Shut-off devices to the safety valve (pres-
surized expansion tank, safety valve, etc.)
are to safe against unintended closing!
- Mount bags to prevent single pipe gravity
circulation.
B1VF1
TT
M K 1
MYK1
RS-T
AF
TopTronic T
3
TT
S L P
WW
KSPFT 2SLVFKSPF
TT
SOP
P
KVLFS 1KVLF
W
KRLF
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhovalhovalhoovalhovallhovalhov
BRU
P
AgroLytlambda
YKR
Y
M 8
T
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalho
T
T
T
M
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalho
HPEY 9
PF
BP1
BP2
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalh
TS F
KW
DHW
CW
Hydr. » Kombinierte HeizungssystemeVerbindungshinweise /
KF
PFBezeichnung /Notation /Denominazione /Désignation
Klemme /Terminal /Morsetti /Bornes
Y9
1 VA1
SOP
VA2
SLV
VE2
SLVF
VE3
KRLF
B1VF1
TT
M K 1
MYK1
TT
S L P
RS-T
AF
TopTronic T
35
B1VF2
TT
M K 2
MYK2
B1VF2
TT
M K 2
MYK2
BP1
WT
TT
P
SOP1
SOP2
KVLFS 1KVLF
W
T
T
KRLF
TSLV
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhovalhovalhoovalhovallhovalhov
BRU
P
AgroLytlambda
YKR
Y
M 8
T
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalho
T
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalho
PF
MY 9
PF2KSPF
T
BP2
Option / opzione
Solar / solaire / solare >~12m2
SLVF
WW
Dies ist ein unerlaubter Weg!Gehen Sie einen Schritt zurück oder löschen Sie dieses Shape!Sie haben die Möglichkeit ein neues Shape zu nehmen!!! hovhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalhovalh
TS F
KW
KSPFT 2SLVFSLVF
min.0,2m2/m2
DHW
CW